| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE GIVE CLARIFICATION ON | | | PANEL"H" 125A MLO IS BEING SHOWN? NEEDS | | | TO HAVE MAIN AND RISER SHOWS IT AS 80A | | | MCB? PLEASE ADJUST. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|