Plan Review Notes
Plan Review Notes For Permit 00071201
Permit Number 00071201
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
  
  
  
 1. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
 2. SUBMIT FLORIDA ENERGY SHEETS SEALED
 AND SIGNED BY OWNER/AGENT.
 3. PROVIDE PRODUCT APPROVAL FOR
 STOREFRONT SYSTEM. METRO DADE COUNTY OR
 SBCCI.
 4. SUBMIT FIRE SPRINKLER APPLICATION
 AND PLANS. FIRE SPRINKLER PERMIT MUST BE
 ISSUED PRIOR TO ISSURANCE OF BUILDING
 PERMIT.
 5. SHEET AI.O WALL DETAIL AND SHEET A1.1
 DETAIL B TYPICAL HANGER REFERS TO ICBO
 NUMBERS, WHAT IS THIS.
 6. SHEET A1-O AND A2.1 REFERS TO ADAAG
 SHOULD BE 1997 FACBC.
 7. ALL WOOD BLOCKING SHALL BE FIRE
 RETADANT.
 8. SHEET AI.0 NOTE ON CORRIDOR WALL
 REFRENCES (UBC 1005.7) CHANGE TO SBC.
 9. SHEET C1.0 TENANT CODE SUMMARY
 CORRECT CODES.
 10. SHEET A3.1 SECTION 1&3 SUPPLY
 STRUSTURAL INFORMATION FOR CONCRETE
 BLOCKING BY TENANT G.C. FOR WIND LOADS
 AND LOADS IMPOSED BY GLAZING SYSTEM.