| 2001-05-09 00:00:00 | REVIEW NOTES:FAILED | | | | | | PLUMBING PLAN REVIEW RESUBMIT UNSAT. | | | 1) BREAK ROOM SINK STILL NOT ADDRESSED | | | FROM PREVIOUS REVIEWS. SHOW ELEVATION | | | DETAILS. | | | | | | 2) SHT PL-1 D/F COMPLY WITH FACBC SECT. | | | 4.1.3 (10) (A), CLEAR FLOOR SPACE, ELEV. | | | DETAIL (PLMB FIXTURE DETAIL SHOWS 34" | | | TO SPOUT, SHOULD BE 36"), PROVISIONS FOR | | | PEOPLE WHO HAVE TROUBLE BENDING OR | | | STOOPING. | | | | | | 3) PLUMBING FIXTURE SCHEDULE SHOWS SK-1 | | | SINK WITH 3-1/4" DRAIN, SHOULD READ | | | 1-1/2". | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|