Plan Review Notes
Plan Review Notes For Permit 00071200
Permit Number 00071200
Review Stop P
Sequence Number 3
Notes
Date Text
2001-05-09 00:00:00REVIEW NOTES:FAILED
  
 PLUMBING PLAN REVIEW RESUBMIT UNSAT.
 1) BREAK ROOM SINK STILL NOT ADDRESSED
 FROM PREVIOUS REVIEWS. SHOW ELEVATION
 DETAILS.
  
 2) SHT PL-1 D/F COMPLY WITH FACBC SECT.
 4.1.3 (10) (A), CLEAR FLOOR SPACE, ELEV.
 DETAIL (PLMB FIXTURE DETAIL SHOWS 34"
 TO SPOUT, SHOULD BE 36"), PROVISIONS FOR
 PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING.
  
 3) PLUMBING FIXTURE SCHEDULE SHOWS SK-1
 SINK WITH 3-1/4" DRAIN, SHOULD READ
 1-1/2".
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377