Plan Review Notes
Plan Review Notes For Permit 00071200
Permit Number 00071200
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO BUILDING ADDRESS NOTED ON
 ELEVATION DRAWINGS.
 2) INTERIOR FINISHES IN EXITS SHALL BE
 CLASS A OR B. INTERIOR FINISHES IN
 OFFICES SHALL BE CLASS A,B OR C.
 3) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, 1985 EDITION.
 4) PROVIDE COMPLETE FIRE ALARM SYSTEM
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS. A SEPARATE PLAN AND PERMIT
 REQUIRED PRIOR TO INSTALLATION.
 5) PROVIDE MORE DETAILS ON THE FIRE
 DEPARTMENT CONNECTION AND HOSE VALVE
 CABINET SHOWN ON PAGE PL1.
 6) WHERE ARE THE FIRE HYDRANTS NEAR
 THE PROPERTY LOCATED.
 7) HAZARDOUS AREAS OR ROOMS TO BE
 PROTECTED BY AT LEAST ONE HOUR FIRE
 RATED CONSTRUCTION WITH RATED FIRE
 DOORS.