2001-01-08 00:00:00***************** UNSAT ****************
  
 **** PLANS NEED TO BE SIGNED AND SEALED*
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%
 FOR LIGHTING ETC.
  
 2)NOTE: PLEASE SEE 220-12-B FOR LOAD
 CALCS ON TRACK LIGHTING.
  
 3)NOTE: YOU SHOW GROUND FROM TRANSFORMER
 GOING TO BLDG STEEL OR COLD WATER.
 PLEASE SEE 250-50
  
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  