| Plan Review Notes For Permit 00071172 |
| Permit Number |
00071172 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL STORAGE ROOMS, ELECTRICAL ROOMS, | | | BATHROOMS, VERTICAL SHAFTS, FOYERS, | | | MECHANICAL ROOMS, AND EXIT VOMITORIES. | | | 2) ON SEPTEMBER 5, 2000, THIS WRITER | | | CALLED RAUL ZORILLA OF QUALITY FIRE | | | CONTROL SYSTEMS, INC., AND REQUESTED CUT | | | SHEETS ON THE FIRE SPRINKLER HEADS | | | PLANNED FOR USE. THE CITY FIRE MARSHAL | | | WILL ALLOW THE USE OF CPVC IN THE | | | SEATING AREA ONLY. | | | 3) THIS PLAN REVIEW DID NOT INCLUDE THE | | | SEATING PLAN FOR THE LOWER ASSEMBLY | | | AREA OF THE BUILDING. |
|