| Plan Review Notes For Permit 00071152 |
| Permit Number |
00071152 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) DOOR TO TOILET (260) INTERFERES WITH | | | EXIT ACCESS CORRIDOR TO SOUTH | | | STAIRTOWER. | | | 2) INTERIOR FINISH IN EXITS SHALL BE | | | CLASS A OR B. INTERIOR FINISHES IN | | | OFFICES CAN BE CLASS A,B, OR C. | | | 3) FIRE ALARM SYSTEM TO BE ADDRESSABLE | | | OR CLASS A. LOCKS ON EGRESS DOORS TIED | | | INTO FIRE ALARM SYSTEM TO COMPLY WITH | | | SPECIAL LOCKING ARRANGEMENTS, NFPA 101, | | | THE LIFE SAFETY CODE, 1985 EDITION. | | | 4) WHEN ACTIVATED, THE FIRE ALARM SYSTEM | | | ON THE SECOND FLOOR IS TO BE AUDIBLE | | | THROUGHOUT SPACE. | | | 5) NO SMOKE DETECTOR (S) SHOWN IN | | | ELEVATOR LOBBY. | | | 6) CORRIDORS USED FOR EXITING MUST BE | | | AT LEAST ONE HOUR FIRE RATED, WHEN | | | OCCUPANCIES OF 30 OR MORE PERSONS ARE | | | PRESENT. | | | 7) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS. A SEPARATE PERMIT IS REQUIRED. | | | 8) PROVIDE FIRE SPRINKLER SYSTEM SHOP | | | DRAWINGS. A SEPARATE PERMIT IS REQUIRED. |
|