Plan Review Notes
Plan Review Notes For Permit 00071152
Permit Number 00071152
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) DOOR TO TOILET (260) INTERFERES WITH
 EXIT ACCESS CORRIDOR TO SOUTH
 STAIRTOWER.
 2) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B. INTERIOR FINISHES IN
 OFFICES CAN BE CLASS A,B, OR C.
 3) FIRE ALARM SYSTEM TO BE ADDRESSABLE
 OR CLASS A. LOCKS ON EGRESS DOORS TIED
 INTO FIRE ALARM SYSTEM TO COMPLY WITH
 SPECIAL LOCKING ARRANGEMENTS, NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION.
 4) WHEN ACTIVATED, THE FIRE ALARM SYSTEM
 ON THE SECOND FLOOR IS TO BE AUDIBLE
 THROUGHOUT SPACE.
 5) NO SMOKE DETECTOR (S) SHOWN IN
 ELEVATOR LOBBY.
 6) CORRIDORS USED FOR EXITING MUST BE
 AT LEAST ONE HOUR FIRE RATED, WHEN
 OCCUPANCIES OF 30 OR MORE PERSONS ARE
 PRESENT.
 7) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS. A SEPARATE PERMIT IS REQUIRED.
 8) PROVIDE FIRE SPRINKLER SYSTEM SHOP
 DRAWINGS. A SEPARATE PERMIT IS REQUIRED.