2001-01-08 00:00:00************* PROVISO ******************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.
  
 2)NOTE: PLEASE SUBMIT ALL AIC RATINGS
 FOR ALL EQUIPMENT. THIS IS TO BE SUBMIT-
 -TED ON E-SHEET AND BY ENGINEER OF RE-
 -CORD.THIS IS TO BE SHOWN ON PLANS.
 A MIN.RATING IS REQ`D. IF A HIGHER AIC
 RATING IS INSTALLED THEN THAT WILL BE
 ACCEPTED. PER 110-9/215-5 OF NEC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  