| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* PROVISO ****************** | | | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. | | | | | | 2)NOTE: PLEASE SUBMIT ALL AIC RATINGS | | | FOR ALL EQUIPMENT. THIS IS TO BE SUBMIT- | | | -TED ON E-SHEET AND BY ENGINEER OF RE- | | | -CORD.THIS IS TO BE SHOWN ON PLANS. | | | A MIN.RATING IS REQ`D. IF A HIGHER AIC | | | RATING IS INSTALLED THEN THAT WILL BE | | | ACCEPTED. PER 110-9/215-5 OF NEC. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|