| Plan Review Notes For Permit 00071117 |
| Permit Number |
00071117 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR MAIN PANEL.PLEASE SHOW ALL LOADS | | | THAT ARE CONTINUOUS LOADS AT 125%. | | | | | | | | | 2)NOTE:PLEASE SEE 220-12-B FOR TRACK | | | LIGHTING CALCS. | | | | | | 3)NOTE: PANEL SCHEDULE SUBMITTED NEEDS | | | TO BE MORE DETAILED ON CORRELATING | | | BRANCH CIRCUIT #`S. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|