2001-01-08 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR MAIN PANEL.PLEASE SHOW ALL LOADS
 THAT ARE CONTINUOUS LOADS AT 125%.
  
  
 2)NOTE:PLEASE SEE 220-12-B FOR TRACK
 LIGHTING CALCS.
  
 3)NOTE: PANEL SCHEDULE SUBMITTED NEEDS
 TO BE MORE DETAILED ON CORRELATING
 BRANCH CIRCUIT #`S.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.