| Plan Review Notes For Permit 00071095 |
| Permit Number |
00071095 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PLEASE PROVIDE INFORMATION ON THE | | | FLOORING TYPE MATERIAL LOCATED WITHIN | | | SPRAY BOOTH. | | | 2) PLEASE INDICATE IF ANY VISION PANELS | | | ARE PRESENT AND WHAT TYPE THEY ARE. | | | 3) HOW IS GROUNDING AND BONDING OF THE | | | SPRAY BOOTH BEING ACCOMPLISHED. | | | 4) PLEASE INDICATE HOW MAKE-UP AIR IS | | | BEING PROVIDED. | | | 5) EXHAUST DUCT TO BE A MINIMUM OF SIX | | | FEET FROM ANY WALL OR ROOF. | | | 6) WHEN THE FIRE SPRINKLER SYSTEM | | | ACTIVATES FOR THE BOOTH, AN AUDIBLE | | | ALARM IS TO BE PROVIDED IF A BUILDING | | | FIRE ALARM SYSTEM IS NOT PRESENT. |
|