| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PASSED WITH PROVISOS | | | SHEET C-2 REQUIRES HANDI CAP ACCESSABILI | | | TY OFF EXECUTIVE CENTER DRIVE | | | SEE MARKED PLAN WHERE HC RAMPS ARE | | | REQUIRED. | | | SHEET C-2 REFLECT DUMPSTER HAVING 12'-0" | | | OPENING.IT IS REQUIRED THAT THE OPENIN | | | G BE 12'-6" MINIMUM. | | | SHEET C-4 | | | CLEAN-OUT REQUIRED ON SANITARY LATERAL | | | SEE PLAN | | | SHEET C-4 | | | DOUBLE DETECTOR CHECK VALVE MUST BE MOVE | | | D CLOSER TO PROPERTY LINE. | | | LIFT STATION INFORMATION MUST BE | | | SUBMITTED TO PUBLIC UTILITIES SO THAT | | | THE LIFT STATION DEPARTMENT REVIEWS IT. | | | ALONG WITH THE SPECIFICATIONS OF ALL | | | EQUIPMENT TO BE INSTALLED. | | | 1000 45TH STREET, | | | WEST PALM BEACH, FL 33407 | | | (561) 659-8040 EXT. 2306 | | | ATTNETION MANNY GONZALEZ |
|