Plan Review Notes
Plan Review Notes For Permit 00071087
Permit Number 00071087
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PASSED WITH PROVISOS
 SHEET C-2 REQUIRES HANDI CAP ACCESSABILI
 TY OFF EXECUTIVE CENTER DRIVE
 SEE MARKED PLAN WHERE HC RAMPS ARE
 REQUIRED.
 SHEET C-2 REFLECT DUMPSTER HAVING 12'-0"
 OPENING.IT IS REQUIRED THAT THE OPENIN
 G BE 12'-6" MINIMUM.
 SHEET C-4
 CLEAN-OUT REQUIRED ON SANITARY LATERAL
 SEE PLAN
 SHEET C-4
 DOUBLE DETECTOR CHECK VALVE MUST BE MOVE
 D CLOSER TO PROPERTY LINE.
 LIFT STATION INFORMATION MUST BE
 SUBMITTED TO PUBLIC UTILITIES SO THAT
 THE LIFT STATION DEPARTMENT REVIEWS IT.
 ALONG WITH THE SPECIFICATIONS OF ALL
 EQUIPMENT TO BE INSTALLED.