| Plan Review Notes For Permit 00071044 |
| Permit Number |
00071044 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | 1.FIRE DAMPERS REQUIRED AT RATED WALLS | | | AS PER 1997 SMC 610.1.2.. | | | 2.PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2.. | | | 3.REQUIRES FLEX DUCT CONNECTION DETAIL. | | | 4.AHU MOUNTING DETAIL TO BE PROVIDED. |
|