| Plan Review Notes For Permit 00071007 |
| Permit Number |
00071007 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO **************** | | | | | | 1)NOTE:PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | FOR COMMERCIAL BUILD OUT SPACE. | | | | | | 2)NOTE: PLEASE NOTE SMOKE DETECTORS ARE | | | REQ`D INSIDE AND OUTSIDE SLEEPING ROOMS. | | | NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. 210-8-A-6 | | | | | | 4)NOTE: PLEASE SEE 210-8 FOR OUTLETS | | | WITHIN AREA OF WET-BAR. | | | | | | 5)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S) 210-11-C-3 ON PANEL | | | SCHEDULES. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE FINAL ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|