2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE:PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%
 FOR COMMERCIAL BUILD OUT SPACE.
  
 2)NOTE: PLEASE NOTE SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE SLEEPING ROOMS.
 NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210-8-A-6
  
 4)NOTE: PLEASE SEE 210-8 FOR OUTLETS
 WITHIN AREA OF WET-BAR.
  
 5)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) 210-11-C-3 ON PANEL
 SCHEDULES.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE FINAL ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372