Plan Review Notes
Plan Review Notes For Permit 00070985
Permit Number 00070985
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
 (ACCORDING TO SQ.FT.OF SPACE & OCCUPANT
 LOAD.)SEE SPC SEC.407.1.3 FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 2)H.C FITTING ROOM SHALL BE EQUIPPED W/
 BENCH FIXED ALONG WALL W/THE LONGER
 DIMENSION PER FACBC SEC.4.35.4.
  
 3)SHOW CLEAR INSIDE DIMENSIONS OF TOILET
 ROOMS.(LXW)COMPLY W/FACBC SEC.4.16.