2001-01-08 00:00:001) FIRE ALARM SYSTEM WHEN ACTIVATED IS
 TO BE AUDIBLE THROUGHOUT SPACE.
 2) SECOND FLOOR BALCONY AREA HAS NO AV
 DEVICES TO NOTIFY OCCUPANTS OF AN ALARM
 CONDITION.
 3) SIGNALS RECEIVED BY CENTRAL STATION
 TO INCLUDE WATERFLOW, ALARM, TAMPER, AND
 TROUBLE.
 4) CENTRAL STATION IS TO BE A LICENSED
 UL LISTED CENTRAL STATION APPROVED BY
 THE FIRE RESCUE DEPARTMENT.
 5) FIRE ALARM SYSTEM TO COMPLY WITH NFPA
 72.
 6) SYSTEM TO BE INSPECTED AFTER
 INSTALLATION BY FIRE RESCUE.