Plan Review Notes
Plan Review Notes For Permit 00070919
Permit Number 00070919
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE:PLEASE SEE LOCAL AMENDMENTS FOR
 OUTLET SPACING ALONG WALL/FIXED GLASS
 PANELS. FLOOR BOXES MAY BE INSTALLED FOR
 THIS REQ`MENT. 210-50
  
 2)NOTE:PLEASE SEE ART 210-62 OF NEC FOR
 SHOW WINDOW OUTLETS REQ`D. LOAD CALCS
 PER 220-12-A
  
 3)NOTE: PLEASE SUBMIT REVISED PANEL
 SCHEDULE WITH BRANCH CIRCUITS THAT
 CORRELATE WITH PLAN LAYOUT.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 OF EXISTING BLDG AND NEW AREA BEING ADD-
 -ED. ALL CONTINUOUS LOADS TO BE FIGURED
 AT 125%. LIGHTING ETC. IF CIRCUITS #`S
 41,42 ARE BEING USED THEN IS PANEL FULL?
 IF SO IT WILL BE REQD TO PLACE SUB PANEL
 TO MAINTAIN TWO SPARE LOCATIONS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
  
 561-659-8096 EXT 8372