| Plan Review Notes For Permit 00070919 |
| Permit Number |
00070919 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE:PLEASE SEE LOCAL AMENDMENTS FOR | | | OUTLET SPACING ALONG WALL/FIXED GLASS | | | PANELS. FLOOR BOXES MAY BE INSTALLED FOR | | | THIS REQ`MENT. 210-50 | | | | | | 2)NOTE:PLEASE SEE ART 210-62 OF NEC FOR | | | SHOW WINDOW OUTLETS REQ`D. LOAD CALCS | | | PER 220-12-A | | | | | | 3)NOTE: PLEASE SUBMIT REVISED PANEL | | | SCHEDULE WITH BRANCH CIRCUITS THAT | | | CORRELATE WITH PLAN LAYOUT. | | | | | | 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | OF EXISTING BLDG AND NEW AREA BEING ADD- | | | -ED. ALL CONTINUOUS LOADS TO BE FIGURED | | | AT 125%. LIGHTING ETC. IF CIRCUITS #`S | | | 41,42 ARE BEING USED THEN IS PANEL FULL? | | | IF SO IT WILL BE REQD TO PLACE SUB PANEL | | | TO MAINTAIN TWO SPARE LOCATIONS. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | | | | 561-659-8096 EXT 8372 |
|