| Plan Review Notes For Permit 00070824 |
| Permit Number |
00070824 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BLD STEEL ALSO.250-50 | | | | | | 2)NOTE: MISSING AIC RATING FOR MAINS/ | | | PANEL.110-9 | | | | | | 3)NOTE: PLEASE LIST BATH(S) CIRCUIT(S) | | | AS PER 210-11-C-3 MUST BE 20 AMP AND #12 | | | AWG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|