| Plan Review Notes For Permit 00070819 |
| Permit Number |
00070819 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | FIRE/SMOKE DAMPER DETAIL AND LOCATION IS | | | REQUIRES AT RATED WALLS. | | | DUCT MATERIAL SCHEDULE REQUIRED. | | | PROVIDE EXHAUST FANS DETAIL. | | | ENERGY EFFICIENCY RATING REQUIRED PER | | | FLORIDA ENERGY EFFICIENCY CODE. |
|