2001-01-08 00:00:00DENIED:
 PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 FIRE/SMOKE DAMPER DETAIL AND LOCATION IS
 REQUIRES AT RATED WALLS.
 DUCT MATERIAL SCHEDULE REQUIRED.
 PROVIDE EXHAUST FANS DETAIL.
 ENERGY EFFICIENCY RATING REQUIRED PER
 FLORIDA ENERGY EFFICIENCY CODE.