| Plan Review Notes For Permit 00070819 |
| Permit Number |
00070819 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT******************* | | | | | | 1)NOTE:PLEASE SUBMIT PANEL "D" WITH | | | COMPLETE INFORMATION ON PANEL LIKE PANEL | | | 'A'. | | | | | | 2)NOTE: PLEASE COMPLETE LOAD CALCULATION | | | -S SHOWING ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING, SHOW WINDOW REC AND ALL LOADS | | | FOR TRACK LIGHTING PER 210-62 AND 220-12 | | | -B. PLEASE ADJUST. | | | | | | 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR | | | ALL EQUIPMENT MAINS AND PANELS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | | | | 659-8096 EXT 8372 |
|