| Plan Review Notes For Permit 00070815 |
| Permit Number |
00070815 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW,BY 94 SPC | | | (1) SHT A-1 PLANS TO BE REVIEWED BY | | | DHBR BEFORE PLUMBING PLAN REVIEW. | | | CONTACT 954-958-5520 FOR PLAN REVIEW. | | | (2) SHT P-1 ALL INDIRECT WASTE TO FLR | | | SINKS, SEC.802 | | | (3) SHT P-1 DISH WASHER & WASTE GRINDER | | | TO BY PASS G/W AND CONNECT TO SANITARY | | | SEWER. LOCAL ORDINANCE #2938-96. | | | (4) SHT P-1&2 PLUMBING FIXTURE & KITCHEN | | | EQUIPMENT LEGEND & SPECIFICATIONS, REQ | | | FOR PLAN REVIEW,SEC.104.2 | | | (5) SHT P-4 CO'S IN GREASE WASTE & | | | SANITARY SYSTEM AS REQ. SEC 710. | | | (5) SHT P-5 EMERGENCY GAS SHUT OFF VALVE | | | MANUAL SHUT OFF VALVE UP STREAM, UNION | | | DOWN STREAM. NFPA-54 1996 SEC5.5.5.4 | | | (6) SHT P-5 INCLUDE ALL PIPE SIZES ON | | | THE WATER & GAS ISOMETRIC, NO MORE THAN | | | 2 PLUMBING FIXTURES ON 1/2" COLD WATER. | | | END OF COMMENTS |
|