| Plan Review Notes For Permit 00070815 |
| Permit Number |
00070815 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER PLANS OR | | | HYDRAULIC CALCULATIONS PROVIDED IN | | | DRAWINGS. | | | 2) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 3) PROVIDE COMPLETE SHOP DRAWINGS FOR | | | THE INSTALLATION OF THE HOOD, DUCT | | | AND EXTINGUISHING SYSTEM. WET CHEMICAL | | | EXTINGUISHING SYSTEMS ARE ONLY SYSTEMS | | | PERMITTED. | | | 4) ALL DOORS USED FOR EXITING TO BE | | | EQUIPPED WITH PANIC HARDWARE. FIRE EXIT | | | HARDWARE TO BE INSTALLED ON FIRE DOORS. | | | 5) PROVISIONS TO BE MADE FOR AT LEAST | | | TWO HANDICAPPED PERSONS. | | | 6) DEFINE WAITING AREA. WAITING AREAS | | | CANNOT INTERFERE WITH EXITING. | | | 7) MAIN ENTRY MUST BE CAPABLE OF | | | PROVIDING EXITING FOR AT LEAST 50 | | | PERCENT OF OCCUPANT LOAD. | | | 8) DEFINE RAMPS AND STAIRS. ANY CHANGE | | | IN ELEVATION LESS THAN 21" SHALL BE BY | | | RAMPS. | | | 9) EXPLAIN EXITING ROUTES. | | | 10) PROVIDE FLAMESPREAD DOCUMENTATION ON | | | BOOTHS AND BRANCHES. | | | 11) SEAT COUNTS ON PAGE ID-1 AND ID-8 | | | DO NOT MATCH. | | | 12) EXPLAIN PLATFORMS. | | | 13) HOW IS THE BASE BUILDING FIRE ALARM | | | SYSTEM HEARD IN TENANT SPACE. | | | 14) PORTABLE FIRE EXTINGUISHERS REQUIRED |
|