| Plan Review Notes For Permit 00070801 |
| Permit Number |
00070801 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | | | | 1)NOTE: UPON FURTHER REVIEW,,,,I HAVE | | | READ YOUR RESPONSE TO AIC RATINGS ON | | | SHEET E-4. PLEASE SEE E-4,,,AIC RATINGS | | | ARE GIVEN FOR BRANCH BREAKERS, NOT PANEL | | | -S OR MAIN? LIKE ORIGINALLY NOTED. | | | PLEASE SEE 110-9/110-10/215-5 | | | MAINS/PANELS ALSO MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. BRANCH BREAKERS | | | ONLY HAVE TO MEET THE SERIES RATINGS( | | | DOWNSTREAM RATINGS) | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELETCRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|