2001-01-08 00:00:00************** PROVISO *****************
  
  
 1)NOTE: UPON FURTHER REVIEW,,,,I HAVE
 READ YOUR RESPONSE TO AIC RATINGS ON
 SHEET E-4. PLEASE SEE E-4,,,AIC RATINGS
 ARE GIVEN FOR BRANCH BREAKERS, NOT PANEL
 -S OR MAIN? LIKE ORIGINALLY NOTED.
 PLEASE SEE 110-9/110-10/215-5
 MAINS/PANELS ALSO MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. BRANCH BREAKERS
 ONLY HAVE TO MEET THE SERIES RATINGS(
 DOWNSTREAM RATINGS)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELETCRICAL PLAN REVIEW.
 561-659-8096 EXT 8372