Plan Review Notes
Plan Review Notes For Permit 00070801
Permit Number 00070801
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00 
 TITLE SHEET-THE PLUMBING CODE IN EFFECT
 IS THE 1994 STANDARD PLUMBING CODE,NOT
 1999.
  
 2)SHT.P-4 SHOWS 2"SANITARY LINE ON SITE
 PLAN DETAIL AND RISER DIAGRAM SHOWS 4".
 CLARIFY.
  
 3)SUBMIT ROOF PLAN SHOWING DISCHARGE OF
 CONDENSATE DRAINS.SHT.P-1 STILL SHOWS
 WASTE STACK UP TO RTU.DELETE STACK AND
 PIPING FROM PLANS IF NOT APPLICABLE.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 4)SHT.P-6-"WATER PIPING "SPECS.-IF
 CALCULATED AIR CHAMBERS ARE TO BE USED
 THEY SHALL COMPLY W/SPC SEC.607.8.3,
 607.8.4.
  
 5)SHT.P-3-CLARIFY LEGEND FOR PIPE
 SYSTEMS.BOTH ARE LABELED AS "1"IN THE
 LEGEND.CORRECTLY IDENTIFY EACH SYSTEM ON
 THE PLAN.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 6)SHT.P-6-MOUNTING HEIGHTS FOR DRINKING
 FOUNTAIN SHALL COMPLY W/FACBC SEC.4.15.
  
 7)CLEARLY SHOW TOILET ROOM DIMENSIONS
 (LXW)ON THE PLANS.THE DIMENSIONS ARE NOT
 SHOWN ON THE TITLE SHEET PER YOUR
 RESPONSE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.