| Plan Review Notes For Permit 00070801 |
| Permit Number |
00070801 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | TITLE SHEET-THE PLUMBING CODE IN EFFECT | | | IS THE 1994 STANDARD PLUMBING CODE,NOT | | | 1999. | | | | | | 2)SHT.P-4 SHOWS 2"SANITARY LINE ON SITE | | | PLAN DETAIL AND RISER DIAGRAM SHOWS 4". | | | CLARIFY. | | | | | | 3)SUBMIT ROOF PLAN SHOWING DISCHARGE OF | | | CONDENSATE DRAINS.SHT.P-1 STILL SHOWS | | | WASTE STACK UP TO RTU.DELETE STACK AND | | | PIPING FROM PLANS IF NOT APPLICABLE. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 4)SHT.P-6-"WATER PIPING "SPECS.-IF | | | CALCULATED AIR CHAMBERS ARE TO BE USED | | | THEY SHALL COMPLY W/SPC SEC.607.8.3, | | | 607.8.4. | | | | | | 5)SHT.P-3-CLARIFY LEGEND FOR PIPE | | | SYSTEMS.BOTH ARE LABELED AS "1"IN THE | | | LEGEND.CORRECTLY IDENTIFY EACH SYSTEM ON | | | THE PLAN.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | 6)SHT.P-6-MOUNTING HEIGHTS FOR DRINKING | | | FOUNTAIN SHALL COMPLY W/FACBC SEC.4.15. | | | | | | 7)CLEARLY SHOW TOILET ROOM DIMENSIONS | | | (LXW)ON THE PLANS.THE DIMENSIONS ARE NOT | | | SHOWN ON THE TITLE SHEET PER YOUR | | | RESPONSE. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|