| Plan Review Notes For Permit 00070801 |
| Permit Number |
00070801 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE ALL ORIGINAL NOTES... | | | NOT ALL NOTES WERE ADDRESSED. | | | | | | 2)NOTE: THE 8 1/2X 11 IS NOT COMPLETE | | | FOR THE LOAD CALCULATIONS REQUESTED. | | | 215-5 | | | ALL THE LOAD CALCS MUST BE ON PLANS FOR | | | JOB.E SHEETS 1-4 FOR EACH PANEL AND | | | MDP | | | 3)NOTE:PANEL SCHEDULES WERE NOT SUBMITT- | | | -ED FOR ALL PANELS AS ASKED FOR ON THE | | | FIRST REVIEW.MUST CORRELATE WITH FLOOR | | | PLANS/LIGHTING LAYOUTS. | | | 4)NOTE: AIC RATINGS FOR ALL EQUIPMENT | | | MAINS/PANELS/BREAKERS. ALL MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER 110- | | | -9 AND 215-5. | | | 5)NOTE:GROUNDING ELECTRODE SYSTEM SHOWN | | | BUT NEEDS TO BE SHOWN TO COLD WATER | | | ALSO/COLD WATER BOND.250-50 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATON | | | FOR REVIEW. | | | PLEASE SUBMIT AFTER ALL REVIEWS HAVE | | | BEEN COMPLETED. NEED TO MAKE TWO COMPL- | | | -ETE SETS FOR REVIEW AND PLEASE KEEP | | | ANY OLD SHEETS THAT MAY HAVE ALREADY | | | BEEN STAMPED AND /OR PASSED BY OTHER | | | TRADES. | | | | | | ONCE AGAIN IF THERE ARE ANY QUESTIONS ON | | | ANY OF THE ELECTRICAL NOTES PLEASE CALL! | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|