Plan Review Notes
Plan Review Notes For Permit 00070801
Permit Number 00070801
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE ALL ORIGINAL NOTES...
 NOT ALL NOTES WERE ADDRESSED.
  
 2)NOTE: THE 8 1/2X 11 IS NOT COMPLETE
 FOR THE LOAD CALCULATIONS REQUESTED.
 215-5
 ALL THE LOAD CALCS MUST BE ON PLANS FOR
 JOB.E SHEETS 1-4 FOR EACH PANEL AND
 MDP
 3)NOTE:PANEL SCHEDULES WERE NOT SUBMITT-
 -ED FOR ALL PANELS AS ASKED FOR ON THE
 FIRST REVIEW.MUST CORRELATE WITH FLOOR
 PLANS/LIGHTING LAYOUTS.
 4)NOTE: AIC RATINGS FOR ALL EQUIPMENT
 MAINS/PANELS/BREAKERS. ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER 110-
 -9 AND 215-5.
 5)NOTE:GROUNDING ELECTRODE SYSTEM SHOWN
 BUT NEEDS TO BE SHOWN TO COLD WATER
 ALSO/COLD WATER BOND.250-50
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATON
 FOR REVIEW.
 PLEASE SUBMIT AFTER ALL REVIEWS HAVE
 BEEN COMPLETED. NEED TO MAKE TWO COMPL-
 -ETE SETS FOR REVIEW AND PLEASE KEEP
 ANY OLD SHEETS THAT MAY HAVE ALREADY
 BEEN STAMPED AND /OR PASSED BY OTHER
 TRADES.
  
 ONCE AGAIN IF THERE ARE ANY QUESTIONS ON
 ANY OF THE ELECTRICAL NOTES PLEASE CALL!
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372