2001-01-08 00:00:001. COVER SHEET: PROJECT DATA SHOWS PLANS
 DESIGNED UNDER 1999 ERITION OF THE
 STANDARD BUILDING,PLUMBING, MECHANICAL,
 FIRE PREVENTION,AND NFPA LIFE SAFETY
 CODES- THE CITY OF WEST PALM BEACH IS
 UNDER THE 1997 SBC,1997 SMC,1994 SPC,
 AND THE 1985 NFPA LIFE SAFETY CODES WITH
 LOCAL AMENDMENTS/ WE DO NOT USE THE
 STANDARD FIRE PREVENTION CODE. PLEASE
 CHANGE PROJECT DATA INFORMATION TO
 REFLECT CORRECT CODES.
 2. SHEET A-6 DETAIL Q SHOWS "ACRYLIC
 BLOCK WINDOWS" IF THESE ARE TO BE USED
 PLEASE SUBMIT INFORMATION AS TO THE FIRE
 RESISTANCE RATING AND WIND LOAD CAPACITY
 SEE SBC 104.2
 3. SUBMIT SPECIFIC DETAILS FOR THE
 EXTERIOR METAL STUD SYSTEM AND DESIGN TO
 BE ANTICIPATED IN SBC 1606.1.1