Plan Review Notes
Plan Review Notes For Permit 00070801
Permit Number 00070801
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SUBMIT MANUF.DATA SHEETS ON WATER
 TREATMENT SYSTEM.WATER SUPPLY SYSTEM
 SHALL BE PROTECTED AGAINST CONTAMINATION
 PER SPC SEC.609.1.
  
 2)SUBMIT OCCUPANT LOAD OF SPACE BASED ON
 SPC TABLE 407.SEE SEC.407.1.3.FOR
 ALLOWED DEDUCTIBLE AREAS.
  
 3)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3.(10)(A).PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
  
 4)FLOOR DRAINS IN TOILET ROOMS SHALL BE
 EQUIPPED W/TRAP PRIMERS PER SPC SEC.
 409.4.1.1.
  
 5)CLEARLY SHOW DIMENSIONS OF ALL TOILET
 ROOMS.(LXW)COMPLY W/FACBC SEC.4.16.2.
  
 6)SINK AND CABINET IN LOUNGE SHALL BE
 HANDICAP ACCESSIBLE AND COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 7)THE MINIMUM NUMBER OF EACH TYPE OF
 PLUMBING FIXTURE SHALL COMPLY W/SPC SEC.
 407.
  
 8)WALLS IN TOILET ROOMS SHALL BE NON-
 ABSORBENT TO A HEIGHT OF 4'PER SBC SEC.
 1204.2.
  
 9)SUBMIT COMPLETE GAS RISER DIAGRAM FOR
 REVIEW AND MANUF.SHEETS FOR GAS EQUIP.
 SEE ATTACHED LIST OF REQS.
  
 10)PLANS REFER TO SITE PLAN FOR CONTIN-
 UATION OF PLUMBING LINES.SITE PLAN IS
 NOT INCLUDED IN SET.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 11)MAXIMUM LENGTH OF INDIRECT WASTE
 LINES SHALL COMPLY W/SPC 805.1.1,805.1.2
 WASTE LINES SHALL BE TRAPPED.
  
 12)CONDENSATE DRAINS FORM RTU'S CANNOT
 DISCHARGE INTO THE SANITARY SYSTEM.
 CONNECTION TO STORM SHALL BE INDIRECT
 AND OUTSIDE OF BUILDING WALLS.SPC 807.2,
 SMC SEC.304.8.3.
  
 13)SUBMIT SIGNED,DATED AND SEALED WATER
 RISER DIAGRAM FOR ALL WORK.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 14)SUBMIT DETAILS ON VENTING OF GAS
 WATER HEATER.SHOW SIZE OF VENT,DISTANCE
 TO TERMINATION PT.,COMPLY W/SGC CHAPT 6.