| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT MANUF.DATA SHEETS ON WATER |
| | TREATMENT SYSTEM.WATER SUPPLY SYSTEM |
| | SHALL BE PROTECTED AGAINST CONTAMINATION |
| | PER SPC SEC.609.1. |
| | |
| | 2)SUBMIT OCCUPANT LOAD OF SPACE BASED ON |
| | SPC TABLE 407.SEE SEC.407.1.3.FOR |
| | ALLOWED DEDUCTIBLE AREAS. |
| | |
| | 3)A DRINKING FOUNTAIN IS REQD.PER SPC |
| | TABLE 407.DRINKING FOUNTAIN SHALL COMPLY |
| | W/FACBC SEC.4.1.3.(10)(A).PROVISIONS |
| | SHALL BE MADE FOR PEOPLE WHO HAVE |
| | TROUBLE BENDING OR STOOPING. |
| | |
| | 4)FLOOR DRAINS IN TOILET ROOMS SHALL BE |
| | EQUIPPED W/TRAP PRIMERS PER SPC SEC. |
| | 409.4.1.1. |
| | |
| | 5)CLEARLY SHOW DIMENSIONS OF ALL TOILET |
| | ROOMS.(LXW)COMPLY W/FACBC SEC.4.16.2. |
| | |
| | 6)SINK AND CABINET IN LOUNGE SHALL BE |
| | HANDICAP ACCESSIBLE AND COMPLY W/FACBC |
| | SEC.4.24.1-4.24.7. |
| | |
| | 7)THE MINIMUM NUMBER OF EACH TYPE OF |
| | PLUMBING FIXTURE SHALL COMPLY W/SPC SEC. |
| | 407. |
| | |
| | 8)WALLS IN TOILET ROOMS SHALL BE NON- |
| | ABSORBENT TO A HEIGHT OF 4'PER SBC SEC. |
| | 1204.2. |
| | |
| | 9)SUBMIT COMPLETE GAS RISER DIAGRAM FOR |
| | REVIEW AND MANUF.SHEETS FOR GAS EQUIP. |
| | SEE ATTACHED LIST OF REQS. |
| | |
| | 10)PLANS REFER TO SITE PLAN FOR CONTIN- |
| | UATION OF PLUMBING LINES.SITE PLAN IS |
| | NOT INCLUDED IN SET.COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.104.2.1. |
| | |
| | 11)MAXIMUM LENGTH OF INDIRECT WASTE |
| | LINES SHALL COMPLY W/SPC 805.1.1,805.1.2 |
| | WASTE LINES SHALL BE TRAPPED. |
| | |
| | 12)CONDENSATE DRAINS FORM RTU'S CANNOT |
| | DISCHARGE INTO THE SANITARY SYSTEM. |
| | CONNECTION TO STORM SHALL BE INDIRECT |
| | AND OUTSIDE OF BUILDING WALLS.SPC 807.2, |
| | SMC SEC.304.8.3. |
| | |
| | 13)SUBMIT SIGNED,DATED AND SEALED WATER |
| | RISER DIAGRAM FOR ALL WORK.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 14)SUBMIT DETAILS ON VENTING OF GAS |
| | WATER HEATER.SHOW SIZE OF VENT,DISTANCE |
| | TO TERMINATION PT.,COMPLY W/SGC CHAPT 6. |