2001-01-08 00:00:00**************DENIED********************
 1. PROVIDE OUSTIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE W/ 1997 SMC 501.2
 3 NO DETAIL FOR EQUIPMENT CURBS ON ROOF
 4. FAN SHUT DOWN REQUIRED BY DUCT SMOKE
 DETECTOR PER 1997 SMC 406 WITH NOTIFICAT
 ION PER NFPA 90A 4-4.4.2 OR 4-4.4.3
 5. MEDICAL GAS REQUIRES MECH PERMIT,
 SUBMIT PLANS AT TIME OF PERMIT APPLICATI
 ON FOR THIS WORK