| Plan Review Notes For Permit 00070801 |
| Permit Number |
00070801 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. PROVIDE OUSTIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE W/ 1997 SMC 501.2 | | | 3 NO DETAIL FOR EQUIPMENT CURBS ON ROOF | | | 4. FAN SHUT DOWN REQUIRED BY DUCT SMOKE | | | DETECTOR PER 1997 SMC 406 WITH NOTIFICAT | | | ION PER NFPA 90A 4-4.4.2 OR 4-4.4.3 | | | 5. MEDICAL GAS REQUIRES MECH PERMIT, | | | SUBMIT PLANS AT TIME OF PERMIT APPLICATI | | | ON FOR THIS WORK |
|