| Plan Review Notes For Permit 00070801 |
| Permit Number |
00070801 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE; PLEASE SUBMIT PANEL SCHEDULE FOR | | | ALL PANELS. | | | | | | 2)NOTE: PLEASE SUBMIT PLANS SHOWING WITH | | | ALL THE REQ`MENTS FOR ARTS:517-50-C-1/ | | | 517-30 -35 SEE FIG.517-30A | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ALL EQUIPMENT BEING INSTALLED. MAINS AND | | | PANELS. 110-9 215-5 | | | | | | 4)NOTE: PLEASE SUBMIT GROUNDING ELECTRO- | | | -DE SYSTEM. | | | | | | 5)NOTE: PLEASE SUBMIT PLANS WITH EQUIP- | | | -MENT LISTINGS. | | | | | | 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR EACH PANEL AND FOR MDP. SHOW ALL | | | CONTINUOUS LOADS AT 125%. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 | | | JAKE LEAHY | | | CHIEF ELECTRICAL INSPECTOR | | | 561-659-8096 EXT 8372 |
|