| Plan Review Notes For Permit 00070798 |
| Permit Number |
00070798 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE PRODUCT APPROVAL FOR: | | | -BUTT GLAZING SYSTEM. | | | -CUSTOM MADE KITCHEN WINDOW ASSEMBLY. | | | -ENTRY DOORS W/ TRANSOM ABOVE ASSEMBLY. | | | -FRENCH DOORS W/ TRANSOM ABOVE ASSEMBLY | | | (SEE COMMENTS ON SUBMITTAL). | | | -S.G.D. WITH TRANSOM ABOVE ASSEMBLY. | | | (SEE COMMENTS ON SUBMITTAL). | | | -GARAGE DOORS PRODUCT APPROVALS THAT | | | MEET THE DESIGN PRESSURES CALCULATED | | | BY THE ARCHITECT. | | | 2-COMPLETELY SPECIFY CEILING CONSTRUCT'N | | | AT ENTRY AND REAR PORCHES, INCLUDING | | | FASTENER TYPES AND SPACING. SECTION | | | 2504 SBC 1997. | | | 3-STORM PANELS TO BE UNDER A SEPARATE | | | PERMIT. (NO INFO. GIVEN AT THIS TIME). | | | 4-TRUSS DRAWINGS: | | | -PROVIDE COMPLETE SET OF ENG'D TRUSS | | | DRAWINGS. | | | -ENGINEER TO SIGN, SEAL AND DATE TRUSS | | | LAYOUT AS WELL. | | | -ARCHITECT TO REVIEW ALL TRUSS DRAWINGS | | | PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | | | | | | | | | | | | NOTES: | | | -PLEASE SUBMITINFORMATION REQUIRED ON | | | PROVISO PRIOR TO CONSTRUCTION OR | | | INSTALLATION TO AVOID DELAYS. |
|