| Plan Review Notes For Permit 00070781 |
| Permit Number |
00070781 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)WALL FINISH IN TOILET ROOM SHALL BE | | | NONABSORBENT TO A HEIGHT OF 4"PER SBC | | | SEC.1204.2. | | | | | | 2)PROVISIONS SHALL BE MADE AT THE DRINK- | | | ING FOUNTAIN FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING.FACBC SEC.4.1.3.(10) | | | (A). | | | | | | 3)SUBMIT INFORMATION/MANUF.SHEETS FOR | | | THE SILVER RECOVERY SYSTEM.DATA IS REQD. | | | REGARDING THE PH OF THE EFFLUENT AND THE | | | DISCHARGE OF THE WASTE.CLEARLY SHOW HOW | | | WASTE IS REMOVED.IF TO THE SANITARY A | | | NEUTRALIZATION TANK MAY BE REQD. | | | ADDITIONAL REQS.MAY BE MANDATED BY CITY | | | OF WPB UTILITIES DEPT.CONTACT ROD COMPO | | | AT 561-835-7423. | | | | | | 4)SHT.E-2-EWH STILL NOTED AS "SUSPENDED | | | FROM STRUCTURE."SUPPLY SHIP'S LADDER | | | AND PLATFORM OR RELOCATE TO FLOOR.SPC | | | SEC.501.7. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|