2001-01-08 00:00:001)WALL FINISH IN TOILET ROOM SHALL BE
 NONABSORBENT TO A HEIGHT OF 4"PER SBC
 SEC.1204.2.
  
 2)PROVISIONS SHALL BE MADE AT THE DRINK-
 ING FOUNTAIN FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.FACBC SEC.4.1.3.(10)
 (A).
  
 3)SUBMIT INFORMATION/MANUF.SHEETS FOR
 THE SILVER RECOVERY SYSTEM.DATA IS REQD.
 REGARDING THE PH OF THE EFFLUENT AND THE
 DISCHARGE OF THE WASTE.CLEARLY SHOW HOW
 WASTE IS REMOVED.IF TO THE SANITARY A
 NEUTRALIZATION TANK MAY BE REQD.
 ADDITIONAL REQS.MAY BE MANDATED BY CITY
 OF WPB UTILITIES DEPT.CONTACT ROD COMPO
 AT 561-835-7423.
  
 4)SHT.E-2-EWH STILL NOTED AS "SUSPENDED
 FROM STRUCTURE."SUPPLY SHIP'S LADDER
 AND PLATFORM OR RELOCATE TO FLOOR.SPC
 SEC.501.7.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.