Plan Review Notes For Permit 00070781
Permit Number 00070781
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)WALL FINISH IN TOILET ROOM SHALL BE
 NONABSORBENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2.(INDICATE TYPE OF PAINT)
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 3)SHT.M-2 NOTES RELIEF AND PAN DRAIN TO
 FLOOR SINK.SINK IS ON RISER BUT NOT ON
 FLOOR PLAN.CLARIFY.
  
 4)HEATER SHALL BE EQUIPPED W/HEAT TRAPS
 PER FLA.ENERGY CODE.
  
 5)HUB DRAINS NOT PERMITTED.FLOOR SINK
 REQD.PER SPC SEC.807.1.
  
 6)SUBMIT INFORMATION /MANUF.SHEETS FOR
 THE SILVER RECOVERY SYSTEM.DATA REQD.
 REGARDING THE PH OF THE EFFLUENT AND
 THE DISCHARGE OF THE WASTE.CLEARLY SHOW
 HOW WASTE IS REMOVED.IF TO THE SANITARY
 A NEUTRALIZATION TANK MAY BE REQD.
 CONTACT R.COMPO AT CITY OF WPB WASTE-
 WATER TREATMENT FACILITY FOR APPROVAL.
 561-835-7423.
  
 7)SHT.M02 AND E-2 STILL NOTE THE EWH AS
 BEING IN THE CEILING.COMPLY W/SPC 501.7.
  
 CALL(561)659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER