| Plan Review Notes For Permit 00070781 |
| Permit Number |
00070781 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | 1) PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE W/ 1997 SMC 501.2 | | | 2) OUTSIDE AIR APPEARS TO BE 371 CFM, | | | EXHAUST AIR IS 900 CFM. SPACE WOULD BE | | | 529 CFM NEG. PROVIDE SOURCE FOR ADDITION | | | TO MAKE UP DIFFERENCE |
|