2001-01-08 00:00:00*************DENIED*********************
 1) PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE W/ 1997 SMC 501.2
 2) OUTSIDE AIR APPEARS TO BE 371 CFM,
 EXHAUST AIR IS 900 CFM. SPACE WOULD BE
 529 CFM NEG. PROVIDE SOURCE FOR ADDITION
 TO MAKE UP DIFFERENCE