Plan Review Notes
Plan Review Notes For Permit 00070765
Permit Number 00070765
Review Stop R
Sequence Number 6
Notes
Date Text
2001-04-12 00:00:00SECOND CHECKLIST TO REVISIONS:
 1-PROVIDE REVISED ENERGY CALCULATIONS
 TO REFLECT REVISIONS (NO DONE FROM
 CHECKLIST DATED 12-18-00).
 2-CEILING FANS:
 -ENGINEER TO REVIEW TABLE 6-6 FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION AND THEN
 CLEARLY INDICATE NUMBER, SIZE AND
 LOCATION OF CEILING FANS (NOT DONE
 FROM PREVIOUS CHECKLIST).
 3-SECTION THRU NEW STAIRS:
 -IT IS NOT CLEAR IF STAIRS PROVIDE THE
 6'-8" HEADROOM CLEARANCE BY EXISTING
 BEAM AREA. IF DRAWINGS ARE DONE TO
 SCALE HOW COME HEADROOM MEASURES 6'-4"
 BUT THE DIMENSION CALLED IS 6'-11".
 VERIFY IN FIELD ACTUAL HEIGHT OF BOTT.
 OF BEAM TO VERIFY HEADROOM.
 -PROVIDE COMPLETE INFORMATION REGARDING
 RAILINGS AND GUARDRAILS AS REQUIRED ON
 SECTION 1007 SBC 1997 (THIS INFO. WAS
 REQUESTED ON PROVISO DATED 9-20-00 BUT
 WAS NEVER PROVIDED)
 4-PROVIDE LANDING AS REQUIRED AT STEPS
 AT REAR SIDE OF THE HOUSE AS
 REQUIRED BY SECTION 1012.1.6 SBC 1997.
 5-SPECIFY SMOKE DETECTORS AT EACH STORY
 AS REQUIRED BY SEC. 905.2.2 SBC 1997.
 6-PROVIDE PRODUCT APPROVAL FOR GARAGE
 DOOR. (GARAGE DOOR WAS NOT PART OF THE
 SCOPE OF WORK ON ORIGINAL APPLICATION)
 7-CONTRACTOR NEEDS TO UPDATE INSURANCE.
 IT EXPIRED ON 2-20-01.
 8-PAY $7.50 ADDITIONAL RADON FEE FOR
 REVISED ADDITIONAL AREA. SEE RECEIPT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.