| 2001-04-12 00:00:00 | SECOND CHECKLIST TO REVISIONS: |
| | 1-PROVIDE REVISED ENERGY CALCULATIONS |
| | TO REFLECT REVISIONS (NO DONE FROM |
| | CHECKLIST DATED 12-18-00). |
| | 2-CEILING FANS: |
| | -ENGINEER TO REVIEW TABLE 6-6 FLORIDA |
| | ENERGY EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION, 1997 EDITION AND THEN |
| | CLEARLY INDICATE NUMBER, SIZE AND |
| | LOCATION OF CEILING FANS (NOT DONE |
| | FROM PREVIOUS CHECKLIST). |
| | 3-SECTION THRU NEW STAIRS: |
| | -IT IS NOT CLEAR IF STAIRS PROVIDE THE |
| | 6'-8" HEADROOM CLEARANCE BY EXISTING |
| | BEAM AREA. IF DRAWINGS ARE DONE TO |
| | SCALE HOW COME HEADROOM MEASURES 6'-4" |
| | BUT THE DIMENSION CALLED IS 6'-11". |
| | VERIFY IN FIELD ACTUAL HEIGHT OF BOTT. |
| | OF BEAM TO VERIFY HEADROOM. |
| | -PROVIDE COMPLETE INFORMATION REGARDING |
| | RAILINGS AND GUARDRAILS AS REQUIRED ON |
| | SECTION 1007 SBC 1997 (THIS INFO. WAS |
| | REQUESTED ON PROVISO DATED 9-20-00 BUT |
| | WAS NEVER PROVIDED) |
| | 4-PROVIDE LANDING AS REQUIRED AT STEPS |
| | AT REAR SIDE OF THE HOUSE AS |
| | REQUIRED BY SECTION 1012.1.6 SBC 1997. |
| | 5-SPECIFY SMOKE DETECTORS AT EACH STORY |
| | AS REQUIRED BY SEC. 905.2.2 SBC 1997. |
| | 6-PROVIDE PRODUCT APPROVAL FOR GARAGE |
| | DOOR. (GARAGE DOOR WAS NOT PART OF THE |
| | SCOPE OF WORK ON ORIGINAL APPLICATION) |
| | 7-CONTRACTOR NEEDS TO UPDATE INSURANCE. |
| | IT EXPIRED ON 2-20-01. |
| | 8-PAY $7.50 ADDITIONAL RADON FEE FOR |
| | REVISED ADDITIONAL AREA. SEE RECEIPT. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 659-8096 EXT. 8232. |