2001-01-08 00:00:00CHECKLIST:
  
 1-ARCHITECT DIDN'T SIGN, SEAL AND DATED
 THE DRAWINGS. CHAPTER 481 FL. STATUTES
  
 2-PROVIDE REVISED ENERGY CALCULATIONS.
  
 3-NEW ELEVATOR:
 -PROVIDE COMPLETE SECTION DETAIL THRU
 ELEVATOR SHAFT. SECTION 104.2.2 OF
 CITY AMENDMENTS TO SBC 1997.
 -PROVIDE COMPLETE SPECIFICATIONS FOR
 ELEVATOR CONFORMING TO ANSI/ASME A17.1
  
 4-SPECIFY NUMBER OF CEILING FANS AS
 REQUIRED BY TABLE 6-6 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING CONST.,
 1997 EDITION. SEE COMMENTS ON PLANS.
  
 5-CORRECT AREA TABULATIONS AS REQUIRED
 WITH NEW ENCLOSED AREA. SEE SHEET R1.
  
 6-SECOND FLOOR WINDOWS AT MASTER BEDRM
 DON'T COMPLY WITH EGRESS REQUIREMENTS
 SECTION 1005.4.4 SBC 1997. REVISE
 WINDOW SCHEDULE AS REQUIRED.
  
 7-SEE COMMENTS ON PLANS. INCLUDING
 COMMENTS BY THE OTHER TRADES.
  
 8-SECTION THRU NEW STAIRS SHOW HEADROOM
 CLEARANCE OF 6'-3" +/-.IT IS NOT
 ALLOWED. MIN. HEADROOM CLEARANCE IS
 6'-8" AS PER SECTION 1007.7 SBC 1997.
 REVISE STAIRS AS REQUIRED.
  
 9-NEED TO OBTAIN A PERMIT FOR MECHANICAL
 WORK. THERE IS NONE APPLIED FOR.
  
 10-ADDITIONAL FEES OF $101.00 ARE DUE
 FOR REVISION UPGRADES. ADDITIONAL
 CONSTRUCTION.
  
  
 NOTES:
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
 -PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW.