| Plan Review Notes For Permit 00070765 |
| Permit Number |
00070765 |
|
| Review Stop |
R |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-STAIRWAY CONSTRUCTION: | | | -REVISE STRUCTURAL DRAWINGS TO MATCH | | | ARCHITECT'S NEW LAYOUT. | | | -PROVIDE COMPLETE INFORMATION REGARDING | | | CONSTRUCTION OF RAILINGS & GUARDRAILS. | | | 2-REVISE ALL ORIGINAL DRAWINGS AS REQ'D. | | | SEE COMMENTS ON PLANS. INCLUDING THOSE | | | BY THE OTHER TRADES. | | | 3-EGRESS WINDOWS AT MASTER BEDROOM NEED | | | TO BE REVISED. (2)17X47 CASEMENT | | | WINDOWS DON'T PROVIDE THE MINIMUM | | | WIDTH REQUIRED. SEC. 1005.4.4 SBC 1997 | | | (THERE'S A MULLION IN BETWEEN). | | | 4-ROOFING, MECHANICAL, ELECTRICAL AND | | | PLUMBING CONTRACTORS NEED TO APPLY FOR | | | THEIR OWN PERMIT. REFERENCE THIS | | | PERMIT APPLICATION NUMBER. |
|