| 2001-01-08 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLANS ARE STILL NOT CORRECT?? |
| | SMOKE DETECTORS ARE REQ`D INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOM PER NFPA-72 |
| | 2-2.1.1.1 NONE SHOWN ON PLANS ???? |
| | ALSO ON EACH LEVEL. |
| | 2)NOTE: PLEASE SEE E-1 SHOWS ELEVATOR |
| | AND NOTES TO RISER? THE RISER SHOWS |
| | EL 2P. IS THIS THE SAME THING? ALSO THE |
| | PANEL SCHEDULE THAT FEEDS EL-2P DOESNOT |
| | SHOW ELEVATOR? PLEASE CLARIFY. |
| | |
| | 3)NOTE: PLEASE NOTE THAT ON 9/20/00 IT |
| | WAS REQ`STED BY THE CONTRACTOR TO THE |
| | BLDG PLAN REVIEWER AND MYSELF THAT THE |
| | PERMIT BE ISSUED WITHOUT THE ELECTRICAL |
| | BEING APPROVED. SEPARATE APPLICATION |
| | AND PLANS WERE REQ`D FOR ELEC. |
| | ON 11/21/00 A MISC ELEC DEMO PERMIT WAS |
| | ISSUED TO ELEC CONTRACTOR BECAUSE HE DID |
| | NOT HAVE PLANS. ONLY MISC ELEC DEMO!!! |
| | PLEASEHAVE ELECTRICAL CONTRACTOR |
| | SUBMIT CORRECTED PLAN WITH HIS PERMIT |
| | APPLICATION. |
| | |
| | 4)NOTE: PLEASE SEE PLANS E-2 SERVICE |
| | CALCS SHOW LOAD AT 236AMPS. A NEW GUTTER |
| | IS SHOWN BUT NO NEW SERVICE CONDUCTORS?? |
| | OR METERCAN AND SIZE. |
| | |
| | 5)NOTE: PLANS ARE NOW SHOWING THE NEW |
| | EQUIPMENT AND NO AIC RATINGS??PER 110-9 |
| | AND 215-5 |
| | |
| | |
| | 6)NOTE: PLEASE NOTE THAT COMPLETE AS- |
| | -BUILTS AND PANEL SCHEDULES ARE REQ`D |
| | BEFORE FINAL ELECTRICAL INSPECTION. |
| | |
| | 7)NOTE: PLEASE SEE NOTES FORM OTHER |
| | REVIEWS. PANEL "B" SHOWN IN CLOSET. |
| | THE PANEL WILL HAVE TO BE MOVED OR THIS |
| | ROOM WOULD HAVE TO BE DEDICATED FOR |
| | ELECTRICAL/ EQUIPMENT. SEE 384-7 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 659-8096 EXT 8372 |