Plan Review Notes For Permit 00070765
Permit Number 00070765
Review Stop E
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLANS ARE STILL NOT CORRECT??
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOM PER NFPA-72
 2-2.1.1.1 NONE SHOWN ON PLANS ????
 ALSO ON EACH LEVEL.
 2)NOTE: PLEASE SEE E-1 SHOWS ELEVATOR
 AND NOTES TO RISER? THE RISER SHOWS
 EL 2P. IS THIS THE SAME THING? ALSO THE
 PANEL SCHEDULE THAT FEEDS EL-2P DOESNOT
 SHOW ELEVATOR? PLEASE CLARIFY.
  
 3)NOTE: PLEASE NOTE THAT ON 9/20/00 IT
 WAS REQ`STED BY THE CONTRACTOR TO THE
 BLDG PLAN REVIEWER AND MYSELF THAT THE
 PERMIT BE ISSUED WITHOUT THE ELECTRICAL
 BEING APPROVED. SEPARATE APPLICATION
 AND PLANS WERE REQ`D FOR ELEC.
 ON 11/21/00 A MISC ELEC DEMO PERMIT WAS
 ISSUED TO ELEC CONTRACTOR BECAUSE HE DID
 NOT HAVE PLANS. ONLY MISC ELEC DEMO!!!
 PLEASEHAVE ELECTRICAL CONTRACTOR
 SUBMIT CORRECTED PLAN WITH HIS PERMIT
 APPLICATION.
  
 4)NOTE: PLEASE SEE PLANS E-2 SERVICE
 CALCS SHOW LOAD AT 236AMPS. A NEW GUTTER
 IS SHOWN BUT NO NEW SERVICE CONDUCTORS??
 OR METERCAN AND SIZE.
  
 5)NOTE: PLANS ARE NOW SHOWING THE NEW
 EQUIPMENT AND NO AIC RATINGS??PER 110-9
 AND 215-5
  
  
 6)NOTE: PLEASE NOTE THAT COMPLETE AS-
 -BUILTS AND PANEL SCHEDULES ARE REQ`D
 BEFORE FINAL ELECTRICAL INSPECTION.
  
 7)NOTE: PLEASE SEE NOTES FORM OTHER
 REVIEWS. PANEL "B" SHOWN IN CLOSET.
 THE PANEL WILL HAVE TO BE MOVED OR THIS
 ROOM WOULD HAVE TO BE DEDICATED FOR
 ELECTRICAL/ EQUIPMENT. SEE 384-7
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372