Plan Review Notes
Plan Review Notes For Permit 00070765
Permit Number 00070765
Review Stop R
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00CHECKLIST
 1-STAIRWAY CONSTRUCTION:
 -REVISE STRUCTURAL DRAWINGS TO MATCH
 ARCHITECT'S NEW LAYOUT, WHICH COMPLIES
 WITH SECTION 1007 SBC 1997.
 -PROVIDE COMPLETE INFORMATION REGARDING
 RAILINGS AND GUARDRAILS CONSTRUCTION
 AND DESIGN.
 2-REVISE ALL ORIGINAL DRAWINGS AS REQ'D
 SEE COMMENTS ON PLANS. INCLUDING THOSE
 BY THE OTHER TRADES.
 3-EGRESS WINDOWS AT MASTER BEDROOM NEED
 TO BE REVISED. (2)17X47 CASEMENT
 WINDOWS DON'T PROVIDE THE MINIMUM
 WITH REQUIRED. SEC. 1005.4.4 SBC 1997.
 (THERE IS A MULLION IN BETWEEN WIND'S)
  
  
  
 NOTES:
 -CONTRACTOR NEEDS TO UPDATE LICENSE.
 -ELECTRICAL, MECHANICAL, PLUMBING AND
 ROOFING CONTRACTORS DIDN'T SIGN THE
 PERMIT APPLICATION. THEREFORE, THEY
 NEED TO APPLY FOR THEIR OWN PERMIT.
 -BUILDING REVIEW WAS APPROVED WITH A
 PROVISO. BUT, SINCE NOT REVISIONS WERE
 DONE TO THE ELECTRICAL AND PLUMBING
 PLANS, THEN, THEY WERE DENIED AGAIN.
 SO, IN ORDER TO EXPEDITE AND FACILITATE
 THE REVIEW PROCESS, IT IS RECOMMENDED
 TO REVISE ALL ORIGINAL DRAWINGS AND
 RE-SUBMIT A COMPLETE PACKAGE FOR ALL
 THE TRADES INVOLVED.
  
 -IMPORTANT: PLEASE RETURN REVIEWED SETS
 AFTER CORRECTIONS ARE DONE IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.