| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING STAMPED DRAWINGS AND RECEIPT. |
| | 2-SITE PLAN INDICATES SOME WORK TO BE |
| | DONE ON THE SIDEWALK. COORDINATE WITH |
| | THE ENGINEERING DEPT. FOR SPECIFIC |
| | REQUIREMENTS PRIOR TO ANY CONSTRUCTION |
| | AT 659-8040. BET. 7:00 AM TO 3:00 PM. |
| | 3-CLEARLY INDICATE ON PLANS WHAT'S NEW, |
| | WHAT IS EXISTING. WHAT IS GOING TO BE |
| | REPLACED, ETC. |
| | -PROVIDE MORE DIMENSIONS. EG OPENING |
| | DIMENSIONS, ETC |
| | -PROVIDE COMPLETE DOOR AND WINDOW SCHED |
| | 4-REVISE ENERGY CALCULATIONS AS REQUIRED |
| | -SCOPE OF WORK IS NOT ONLY THE ADDITION |
| | ON SECOND FLOOR, BUT THE WHOLE HOUSE |
| | IS GOING TO BE CONSIDERABLY RENOVATED. |
| | SEC. 600.1.C.1 AND 600.1.C.2 FLORIDA |
| | ENERGY EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | -OWNER TO SIGN AND DATE THIS FORM TOO. |
| | 5-REVISE DESIGN CERTIFICATION FOR BLDG |
| | CODE COMPLIANCE FORM:(STRUCTUR'L ENGR) |
| | -THIS IS A TWO STORY HOUSE. MEAN ROOF |
| | HEIGHT IS 24'-8" PLUS OR MINUS. REVISE |
| | THE BASIC VELOCITY PRESSURE AS REQ'D |
| | 6-MASTER BEDROOM AND BEDROOMS #1 AND #2: |
| | -MUST MEET EGRESS REQUIREMENTS AS PER |
| | SECTION 1005.4.4 SBC 1997. |
| | 7-AT LEAST ONE COMPLETE BATHROOM ON 1ST |
| | FLOOR MUST HAVE A DOOR THAT PROVIDES |
| | 29" MINIMUM CLEAR OPENING. SECTION 11 |
| | FLORIDA ACCESSIBILITY CODE FOR BLDG. |
| | CONSTRUCTION, 1997 EDITION. |
| | 8-STORM PANELS: |
| | -PROVIDE A COMPLETE INSTALLATION SCHED. |
| | AS PER CITY SAMPLE ATTACHED AND A |
| | COMPLETE KEY PLAN. |
| | -PROVIDE A COMPLETE CURRENT PRODUCT |
| | APPROVAL REPORT AND DRAWINGS AND |
| | HIGHLIGHT SPECIFIC MOUNTING CONDITIONS |
| | AND ANCHORS TO BE USED ACCORDING TO |
| | THE MEAN ROOF HEIGHT,DESIGN PRESSURES, |
| | PANEL SPAN, EDGE DISTANCE AND |
| | STRUCTURE TO BE ATTACHED TO (CONCRETE |
| | OR CONCRETE BLOCK). |
| | 9-SPECIFY THE DESIGN PRESSURES THAT |
| | WERE CALCULATED AT ALL EXTERIOR |
| | OPENINGS. SECTION 1606 SBC 1997. |
| | 10-NEW STAIR CONSTRUCTION: |
| | -NEED MORE INFORMATION LIKE DIMENSIONS, |
| | RISER TREAD RATIO, RAILINGS ECT. |
| | SEE SECTION 1007 SBC 1997. |
| | -STAIRS NEED TO BE REVISE TO COMPLY W/ |
| | THE FOLLOWING SECTIONS: 1007.6.2 - |
| | 1007.6.3 - 1007.7 - 1007.8.1 OF SBC/97 |
| | 11-PROVIDE SAFETY GLASS AT LIVING ROOM |
| | AND MASTER BATHRM. SEC 2405.2 SBC 1997 |
| | 12-PROVIDE CURRENT PRODUCT APPROVALS FOR |
| | FLAT ROOF SYSTEM AND BARREL TILE |
| | (CLEARLY INDICATE SYSTEM AND FASTENING |
| | TO BE USED). |
| | 13-WINDOWS & DOORS SITE SPECIFIC PRODUCT |
| | APPROVALS: |
| | -ENGINEER WHO SIGNED ITEM #10 IS NOT |
| | THE PROFESSIONAL ENGINEER OF RECORD. |
| | -ITEMS #9 AND #10: ENGINEERS TO CLEARLY |
| | PROVIDE NAME, LICENSE NUMBER AND |
| | ADDRESS AS PER CHAPTER 471 OF FLORIDA |
| | STATUTES. |
| | -CLARIFY WHY ITEM #4.1.E.IV DOES NOT |
| | CONSIDER THE BUCK TO BE STRUCTURAL IF |
| | THE SPECIFIC INSTALLATION REQUIREMENTS |
| | SPECIFIES ATTACHMENT OF WINDOW OR DOOR |
| | TO THIS BUCK. |
| | -CLEARLY SPECIFY MODEL |
| | 14-PROVIDE HANDRAILS AT STEPS LEADING |
| | TO POOL DECK. SEC 1007.5 SBC 1997. |
| | 15-CLEARLY SPECIFY SIZES OF CEILING FANS |
| | AS PER TABLE 6-6 OF FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION, 1997 EDITION. |
| | 16-SEE PLANS FOR ADDITIONAL COMMENTS, |
| | INCLUDING THOSE BY THE OTHER TRADES. |
| | 17-UPDATE SOIL TEST REPORT. WE ADOPTED |
| | THE 1997 SBC. SEE SHEET #1 OF REPORT. |
| | |
| | |
| | |
| | |
| | NOTE: |
| | |
| | PLEASE RETURN REVIEWED SETS AFTER ALL |
| | REVISIONS/CORRECTIONS ARE DONE IN ORDER |
| | TO EXPEDITE THE REVIEW PROCESS. |