2001-01-08 00:00:00************** UNSAT ******************
  
 PLEASE NOTE THAT MORE THAN 50% OF THE
 ELECTRICAL WORK IS BEING DONE. PLEASE
 NOTE :ALL ELECTRICAL WILL HAVE TO BE
 BROUGHT UP TO CODE.
  
 1)NOTE: PLEASE SHOW ALL EXISTING AND
 NEW MEAMS OF EGRESS LIGHTING PER 210-70
  
 2)NOTE: SMOKE DETECTORS WILL BE REQ`D
 PER NFPA-72 2-2.1.1.1 INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS. AND EACH LEVEL OF
 MULTI-LEVEL DWELLING.
  
 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210-8-A-6
  
 4)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 PLEASE SHOW PANEL "D" MCB . YOU SAY IT
 IS BEING FED BY 100 MCB ?? WHERE IS THIS
 E-3 SHOWS PANEL B?? WHERE IS THIS ON
 RISER DIADGRAM.
  
 5)NOTE: PLEASE SHOW LOCATION OF ALL
 EQUIPMENT/PANELS/MAINS ETC.
 MAINS MUST BE GROUPED PER 230-72
 PLEASE GIVE CLARIFICATION ON SERVICE
 ENTRANCE CONDUCTORS. COPPER/ALUM?
 YOU SHOW LOAD AT 222 AMPS AND NO ROOM
 FOR SPARE LOAD.PLEASE SHOW LOADS ON EACH
 PANEL.
  
 6)NOTE: PLEASE SHOW EXISTING ELECTRICAL
 OUTLETS ETC.SPACING SHALL BE BROUGHT UP
 TO CODE. PER 210-52
 7)NOTE: PLEASE SHOW EXISTING GROUNDING
 ELECTRODE SYSTEM.215-5
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
  
 659-8096 EXT 8372