| 2001-01-08 00:00:00 | ************** UNSAT ****************** |
| | |
| | PLEASE NOTE THAT MORE THAN 50% OF THE |
| | ELECTRICAL WORK IS BEING DONE. PLEASE |
| | NOTE :ALL ELECTRICAL WILL HAVE TO BE |
| | BROUGHT UP TO CODE. |
| | |
| | 1)NOTE: PLEASE SHOW ALL EXISTING AND |
| | NEW MEAMS OF EGRESS LIGHTING PER 210-70 |
| | |
| | 2)NOTE: SMOKE DETECTORS WILL BE REQ`D |
| | PER NFPA-72 2-2.1.1.1 INSIDE AND OUTSIDE |
| | ALL SLEEPING ROOMS. AND EACH LEVEL OF |
| | MULTI-LEVEL DWELLING. |
| | |
| | 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED. 210-8-A-6 |
| | |
| | 4)NOTE: PLEASE SUBMIT PANEL SCHEDULES |
| | PLEASE SHOW PANEL "D" MCB . YOU SAY IT |
| | IS BEING FED BY 100 MCB ?? WHERE IS THIS |
| | E-3 SHOWS PANEL B?? WHERE IS THIS ON |
| | RISER DIADGRAM. |
| | |
| | 5)NOTE: PLEASE SHOW LOCATION OF ALL |
| | EQUIPMENT/PANELS/MAINS ETC. |
| | MAINS MUST BE GROUPED PER 230-72 |
| | PLEASE GIVE CLARIFICATION ON SERVICE |
| | ENTRANCE CONDUCTORS. COPPER/ALUM? |
| | YOU SHOW LOAD AT 222 AMPS AND NO ROOM |
| | FOR SPARE LOAD.PLEASE SHOW LOADS ON EACH |
| | PANEL. |
| | |
| | 6)NOTE: PLEASE SHOW EXISTING ELECTRICAL |
| | OUTLETS ETC.SPACING SHALL BE BROUGHT UP |
| | TO CODE. PER 210-52 |
| | 7)NOTE: PLEASE SHOW EXISTING GROUNDING |
| | ELECTRODE SYSTEM.215-5 |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL |
| | |