Plan Review Notes
Plan Review Notes For Permit 00070716
Permit Number 00070716
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-MEAN ROOF HEIGHT IS INCORRECT. SEE
 ARCHITECTURAL DRAWINGS.
 2-REVISE CONNECTORS FOR TRUSSES T22, S1.
 SEE ENGINEERED TRUSS DRAWINGS.
 3-SPECIFY WOOD TO WOOD CONNECTORS AT
 FRONT AND BACK PORCHES. SEE TRUSS
 LAYOUT.
 4-ARCHITECT TO PROVIDE A REVISED ROOF
 FRAMING PLAN CLEARLY SPECIFYING THE
 REQUIRED CONNECTORS. SEE TRUSS LAYOUT
 FOR COMMENTS.
  
  
  
 * IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT
 659-8096 EXT. 8232.