Plan Review Notes
Plan Review Notes For Permit 00070686
Permit Number 00070686
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) PLEASE ADDRESS PREVIOUS COMMENT
 DATED 9-18-00 & 10-05-00 BY T LARGE
 A/C CONDENSATE IS NOT ALLOWED TO
 DISCHARGE TO SANITARY SEWER.
 CONNECT TO DRY WELL,PLANTER,STORM
 DRAINAGE OUT SIDE OF BUILDING.
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096 X 8233