Plan Review Notes
Plan Review Notes For Permit 00070686
Permit Number 00070686
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:001)SHT.P1.1-FLAT DRY VENTS ARE NOT
 PERMITTED PER SPC SEC.906.2.1.SEE F-2.
  
 2)WASTE FROM HVAC UNITS SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM.
 CONNECTION TO THE STORM SYSTEM SHALL BE
 INDIRECT AND OUTSIDE THE BUILDING WALLS.
 SPC SEC.804.3.
  
 3)ALL SHEETS SHALL BE SIGNED AND SEALED
 BY THE ENGINEER OF RECORD PER
 FAC 61G15-23.002.,F.S.471.025(1)
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.