| Plan Review Notes For Permit 00070686 |
| Permit Number |
00070686 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SHT.P1.1-FLAT DRY VENTS ARE NOT | | | PERMITTED PER SPC SEC.906.2.1.SEE F-2. | | | | | | 2)WASTE FROM HVAC UNITS SHALL NOT | | | DISCHARGE TO THE SANITARY SYSTEM. | | | CONNECTION TO THE STORM SYSTEM SHALL BE | | | INDIRECT AND OUTSIDE THE BUILDING WALLS. | | | SPC SEC.804.3. | | | | | | 3)ALL SHEETS SHALL BE SIGNED AND SEALED | | | BY THE ENGINEER OF RECORD PER | | | FAC 61G15-23.002.,F.S.471.025(1) | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|