2001-01-08 00:00:001)A LAVATORY IS REQD.IN THE ACCESSIBLE
 TOILET STALLS PER FACBC SEC.4.17.3.AND
 THE MIN.WIDTH SHALL BE AS FACBC SEC.
 4.17.3.
  
 2)SUBMIT OCCUPANT LOAD BASED ON
 HABITABLE FLOOR SPACE PER SPC 407.SEE
 SEC/407.1.3. FOR ALLOWED DEDUCTIBLE
 AREAS.
  
 3)THE URINAL SHALL BE INSTALLED AT
 HANDICAP HEIGHT.COMPLY W/FACBC SEC.4.18.
  
 4)WASTE FROM HVAC UNITS SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM.
 CONNECTION TO THE STORM SYSTEM SHALL BE
 INDIRECT OUTSIDE THE BUILDING WALLS.
 SPC SEC.804.3.
  
 5)BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED W/A VACUUM RELIEF LINE
 INSTALLED PER MANUF.RECOMMEND. AND SPC.
  
 6)FLAT DRY VENTS ARE NOT PERMITTED PER
 SPC SEC.906.2.1.SEE MOP SINK
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER