| Plan Review Notes For Permit 00070686 |
| Permit Number |
00070686 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)A LAVATORY IS REQD.IN THE ACCESSIBLE | | | TOILET STALLS PER FACBC SEC.4.17.3.AND | | | THE MIN.WIDTH SHALL BE AS FACBC SEC. | | | 4.17.3. | | | | | | 2)SUBMIT OCCUPANT LOAD BASED ON | | | HABITABLE FLOOR SPACE PER SPC 407.SEE | | | SEC/407.1.3. FOR ALLOWED DEDUCTIBLE | | | AREAS. | | | | | | 3)THE URINAL SHALL BE INSTALLED AT | | | HANDICAP HEIGHT.COMPLY W/FACBC SEC.4.18. | | | | | | 4)WASTE FROM HVAC UNITS SHALL NOT | | | DISCHARGE TO THE SANITARY SYSTEM. | | | CONNECTION TO THE STORM SYSTEM SHALL BE | | | INDIRECT OUTSIDE THE BUILDING WALLS. | | | SPC SEC.804.3. | | | | | | 5)BOTTOM FED WATER HEATERS SHALL BE | | | EQUIPPED W/A VACUUM RELIEF LINE | | | INSTALLED PER MANUF.RECOMMEND. AND SPC. | | | | | | 6)FLAT DRY VENTS ARE NOT PERMITTED PER | | | SPC SEC.906.2.1.SEE MOP SINK | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER |
|