Plan Review Notes
Plan Review Notes For Permit 00070686
Permit Number 00070686
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)A LAVATORY IS REQD.IN THE ACCESSIBLE
 STALLS PER FACBC SEC.4.1.6(B).SHOW
 LENGTH AND WIDTH OF STALLS.COMPLY W/
 FACBC SEC.4.17.3,(MIN.WIDTH IS 83")AND
 FIG.30.
  
 2)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S RESTROOM PER SPC TABLE 407.
  
 3)URINAL SHALL BE INSTALLED AT HANDICAP
 HEIGHT.COMPLY W/FACBC SEC.4.18.
  
 4)WASTE FROM HVAC UNITS SHALL NOT
 DISCHARGE TO THE SANITARY.CONNECTION TO
 STORM SYSTEM SHALL BE BY INDIRECT OUT-
 SIDE OF BUILDING WALL.
  
 5)BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED W/A VACUUM RELIEF VALVE PER SPC
 507.1.2.