Plan Review Notes
Plan Review Notes For Permit 00070686
Permit Number 00070686
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:
 1.DAMPERS REQUIRED AT RATED WALLS AS PER
 1997 SMC 610.1.2.. PROVIDE DETAIL.
 2.AIR BALANCE SCHEDULE REQUIRED AS PER
 1997 SMC 501.2..
 3.PROVIDE OUTSIDE AIR CALCULATION PER
 ASHRAE 62-89.
 4.FCU DATA REQUIRED FOR REVIEW.
 5.FAN SHUT DOWN REQUIRED PER NFPA 90A
 4.4.4.2 & 4.4.4.3..
 6.EXHAUST FANS DETAIL REQUIRED.
 7.FLEX DUCT CONNECTION DETAIL TO BE
 PROVIDED.