2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH LOAD
 CALCUATIONS PER 220. PLEASE FIGURE ALL
 CONTINUOUS LOADS AT 125% (LIGHITNG,IT/
 SECURITY ETC) ALSO PLEASE DO NOT LIST AS
 ESTAMATED LOAD.
  
 2)NOTE:PLEASE CALRIFY THE SERVICE. YOU
 ARE SHOWING DELETION OF ATS/GEN/ETC.
 YOU ARE ALSO SHOWING THE 400 AMP PANEL
 AS MLO? WHERE IS MAIN? PLEASE PROVIDE A
 ONE-LINE DIAGRAM OF SERVICE.
  
 3)NOTE: PLEASE PROVIDE ROOF TOP OUTLET
 PER 210-63
  
 4)NOTE: PLEASE SHOW OUTLETS SERVING BATH
 (S) AS GFI/GFI PROTECTED. PER 210-8
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  