| Plan Review Notes For Permit 00070686 |
| Permit Number |
00070686 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH LOAD | | | CALCUATIONS PER 220. PLEASE FIGURE ALL | | | CONTINUOUS LOADS AT 125% (LIGHITNG,IT/ | | | SECURITY ETC) ALSO PLEASE DO NOT LIST AS | | | ESTAMATED LOAD. | | | | | | 2)NOTE:PLEASE CALRIFY THE SERVICE. YOU | | | ARE SHOWING DELETION OF ATS/GEN/ETC. | | | YOU ARE ALSO SHOWING THE 400 AMP PANEL | | | AS MLO? WHERE IS MAIN? PLEASE PROVIDE A | | | ONE-LINE DIAGRAM OF SERVICE. | | | | | | 3)NOTE: PLEASE PROVIDE ROOF TOP OUTLET | | | PER 210-63 | | | | | | 4)NOTE: PLEASE SHOW OUTLETS SERVING BATH | | | (S) AS GFI/GFI PROTECTED. PER 210-8 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|