| Plan Review Notes For Permit 00070639 |
| Permit Number |
00070639 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | 1.PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2... | | | 2.REQUIRE DUCT MATERIAL SCHEDULE. | | | 3.EXHAUST FAN DETAIL REQUIRED ON PLANS. | | | 4.PROVIDE ENERGY EFFFICIENCY RATING OF | | | THE AHU-1 AS PER FLORIDA ENERGY EFFICI- | | | ENCY CODE. | | | 5.PROVDE CFM VALUE OF AHU TO MATCH THE | | | TOTAL OF CFM ON THE PLANS 6550 CFM... |
|