| Plan Review Notes For Permit 00070635 |
| Permit Number |
00070635 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SEE ATTACHED FOR REQS.FOR GREASE TRAP. | | | | | | 2)A WATER USE PERMIT IS REQD.FROM SO.FLA | | | WATER MNGMT.DISTRICT FOR THE IRRIGATION | | | SYSTEM PER FLA.STATUTE 373.219.SUBMIT | | | COPY OF PERMIT. | | | | | | 3)SHT.IR-1-SHOW LOCATION OF RAIN SENSOR | | | ON IRRIGATION SYSTEM. | | | | | | 4)1/2 THE AREA OF ANY VERTICAL WALL | | | (PARAPET) WHICH DIVERTS RAIN WATER TO | | | THE ROOF SHALL BE ADDED TO THE ROOF AREA | | | PER SPC SEC.1108.3.SHOW THIS IN YOUR | | | CALCULATIONS. | | | | | | 5)THE ADJUSTMENT IN YOUR CALCULATIONS | | | SHALL BE MADE TO THE SQUARE FOOTAGE | | | LISTED IN TABLES 1108.1 AND 1108.2 OF | | | THE SPC,NOT TO THE SQUARE FOOTAGE OF | | | THE ROOF.RECALCULATE YOUR PIPE SIZES. | | | | | | 6)SIZE OF FUTURE GREASE TRAPS SHALL BE | | | APPROVED BY CITY OF WPB WASTEWATER DIV. | | | CONTACT R.COMPO AT 561-835-7423. |
|