Plan Review Notes
Plan Review Notes For Permit 00070635
Permit Number 00070635
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: YOU ARE SHOWING PARALLELED
 600MCM FOR SERVICE BUT ONLY SHOWING
 1/0`S FOR NEUTRAL.?
 NEUTRAL LOAD IS SHOWN ALOT HIGHER THAN
 THE CONDUCTORS ARE RATED.
 PLEASE CORRELATE WIRE WITH LOADS SHOWN.
 PER 310-16
  
 2)NOTE: PLEASE SUBMIT AND SHOW LOAD
 CALCULATION FOR HOUSE PANEL TO INCLUDE
 ALL CONTINUOUS LOADS AT 125% (LIGHTING)
 ETC.
  
 3)NOTE: YOU HAVE SUBMITTED PLANS SHOWING
 BRKRS IN PANEL AT 10,000 AIC. PLEASE
 GIVE AIC RATING OF MAIN. PER110-9
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FORREVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372