Plan Review Notes
Plan Review Notes For Permit 00070571
Permit Number 00070571
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)AN ADDITIONAL WATER CLOSET OR URINAL
 IS REQD.IN THE MALE RESTROOM AND A WATER
 CLOSET IS REQD.IN THE FEMALE RESTROOM
 PER SPC TABLE 407 BASED ON THE OCCUPANT
 LOAD OF 199 PERSONS.
  
 2)CLARIFY THE REDUCTION OF THE GAS
 SUPPLY LINES FROM 1"TO 3/4" FOR EACH
 PIECE OF EQUIPMENT.THE PIPE SHALL REMAIN
 FULL SIZE UP TO THE GAS VALVE.SGC 305.4
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.