| Plan Review Notes For Permit 00070571 |
| Permit Number |
00070571 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)AN ADDITIONAL WATER CLOSET OR URINAL | | | IS REQD.IN THE MALE RESTROOM AND A WATER | | | CLOSET IS REQD.IN THE FEMALE RESTROOM | | | PER SPC TABLE 407 BASED ON THE OCCUPANT | | | LOAD OF 199 PERSONS. | | | | | | 2)CLARIFY THE REDUCTION OF THE GAS | | | SUPPLY LINES FROM 1"TO 3/4" FOR EACH | | | PIECE OF EQUIPMENT.THE PIPE SHALL REMAIN | | | FULL SIZE UP TO THE GAS VALVE.SGC 305.4 | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|